+86-182-9191-0663 丨  sales@hiltechgroup.com | support@hiltechgroup.com
About Us

Since 1998 丨 HILTECH®

You are here: Home » Products » Temperature Measuring Instrument » Temperature Transmitter » Panel Mount Temperature Transmitters

Panel Mount Temperature Transmitters

loading

Share to:
facebook sharing button
twitter sharing button
line sharing button
wechat sharing button
linkedin sharing button
pinterest sharing button
sharethis sharing button
  • Inputs : Resistance thermometers (RTD) : Pt100, Pt500, Pt1000, Cu53, Cu100, Ni100, Ni500, Ni1K, Resistance : 0~5000 ohms (range, programmable)
  • Input selection : Via PC software
  • High performance, high reliability
  • Operating ambient : -40 to +85 °C
  • Slim 12.5 mm DIN rail mounting enclosure
Availability:
Quantity:

Panel Mount or DIN Rail Mount Temperature Transmitters Introduction

 A DIN rail is used to mount switches, relays, and transmitters. The rail itself is a piece of metal that is shaped to enable a device (such as a transmitter) to be attached using a spring clip, which slides into a bend in the metal rail and secures itself. The metal rail, complete with attached transmitter, can then be attached to a panel or a wall. The acronym DIN stands for Deutsches Institut fur Normung, which is the German Institute for Standardization. DIN rail transmitters, also called panel mount transmitters, are usually found in diverse applications because they are relatively low-cost and can operate with an array of different sensors. Because of the DIN rail configuration, they are also easy to install. They are somewhat less accurate than weather- and explosion-proof transmitters because of the longer wiring configuration necessary for securing the transmitter. For temperature transmitters, rail mounting is the oldest mounting method.


Panel Mount or DIN Rail Mount Temperature Transmitters Feature

  • 12.5mm slim Din-rail enclosure

  • 2-wire, 4~20mA output with HART

  • Universal input - Thermocouple, RTD, Resistance, Voltage

  • 7.5 to 48 VDC supply voltage range

  • -20 to +85 °C operating temperature

  • 2KV AC RMS galvanic isolation

  • Resistance input upto 5K

  • Voltage input up-to 1000mV

  • Active temperature compensation


Panel Mount or DIN Rail Mount Temperature Transmitters Specification


  

Input

Input Signal

PT100,Cu50 and other RTD signals

RTD Excitation Voltage

2.5V

Allowed Line Resistance

≤100Ω

Output
Output Signal

4-20mA;0-20mA;0-10mA;0-5V;0-10V;1-5V;Customized

 

Output Load Resistance

RL≤500Ω(output current signal);

RL≥1KΩ(output voltage signal);

Other Parameters
Power Supply

DC24V,±10%;AC85-265V

 

Current Consumption

≤70mA(1 in 1 out,24V power supply,output 20mA);

≤90mA(1 in 2out,24V power supply,output 20mA);

≤100mA(2 in 2 out,24V power supply,output 20mA);

Accuracy

0.2%F.S.

Temperature Drift0.005%F.S./℃ (-20℃~+55℃)
Isolation Intensity1500V AC/1min(between input-ouput-power)
Insulation Resistance≥100MΩ(between input-ouput-power)
Working Temperature & Humidity-20℃~+55℃
EMCComplies with GB/T 18268(IEC61326-1)
Applicable Equipment2-wires or 3-wires RTD


-Manuals

Panel Mount or DIN Rail Mount Temperature Transmitters 

-Data sheet


Panel Mount or DIN Rail Mount Temperature Transmitters Application


Field of application

Unsurpassed reliability, accuracy and long-term stability in critical processes over all industries. The configurable transmitter not only transfers converted signals from resistance thermometers (RTD) and thermocouples (TC), it also transfers resistance and voltage signals using HART® communication. Swift and easy operation, visualization and maintenance by PC using operating software. Space-saving DIN rail mounting according to IEC 60715 


Temperature transmitter with HART® -Protocol for converting various input signals into a scalable 4 to 20 mA analog output signal


Input:


Resistance thermometer (RTD)


Thermocouple (TC)


Resistance transmitter (Ω)


Voltage transmitter (mV)