+86-182-9191-0663 丨  sales@hiltechgroup.com | support@hiltechgroup.com

About Us

Since 1998 丨 HILTECH®

You are here: Home » Products » Valves,Actuators & Regulators & Pumps » Fire Pump » Vertical Turbine Fire Pump

Vertical Turbine Fire Pump

Share to:
  • UL Listed/FM Approved/NFPA-20 Design
  • For Commercial, Industrial and Marine Use
  • Special Materials for Seawater Applications
  • Diesel and Electric Driven
Availability:
Quantity:

Vertical Turbine Fire Pump Introduction

Vertical Turbine Fire Pump have submerged impellers contained in a series -bowl assembly at the bottom of a vertical shaft. The design is similar to pumps used extensively for industrial and municipal service.

 

These pumps are UL & FM approved for discharging water from lakes, streams, open sumps, drilled wells and other equivalent subsurface sources. each pump consists of a discharge head, motor stand, column pipe, line shaft, bowl assembly and suction strainer.

Vertical Turbine Fire Pump Feature

  • With advanced hydraulic design and structure, adopting ashland process to make impeller blade, adopting epoxy coating process in impeller vane, and reasonable selection of materials to make the products have an excellent performance and long service life. 


  • Whirl sand device and maze-like structure make the sand unable to enter the bearings.


  • Impeller shaft and motor shaft both adopt the bronze bearing as theri supporting. The radial run-out of the shaft is less than 0.13mm which meets US standard. These make the pump have a smooth and reliable operation and low noise.


  • The discharge head has a beautiful shape and big window. It's convenient to repair and replace the gland.


  • Material from ductile iron GGG60, SS304 or SS316 for optional.

  • UL listed and FM approved pump for suction lift conditions

  • Minimal maintenance

  • Can be used where city water is not available and ponds or lakes are the only water supply

  • Construction materials for seawater service are available


Vertical Turbine Fire Pump Specification 

Performance Range

Capacity: 40-1260m³/h

Rated pressure: 1.5Mpa

When punping clean water or physical and chemical liquid: Neutral water, PH=6.5-8.5, chloride ion content:=400mg/L, medium temperature:=40ºC


Material of Vertical Turbine Fire Pump

Bowl: Cast iron, Stainless steel

Shaft: Stainless steel

Impeller: Cast iron, Bronze or Stainless steel

Discharge head: Cast iron or carbon steel

NO.Pump Model / Outlet Size / Min SubmergenceFlowHead
(usgpm)(psi)(m)
1100VTP40~6
Outlet Size 4" Min Submergence
10040~27028~190
15040~26328-185
20040~25928~182
25040~25328~178
2150VTP200~17
Outlet Size 6" Min Submergence
50040~21328~150
75040~18232~24
50040~23028~162
75045~18844~32
3200VTP250~22
Outlet Size 8" Min Submergence
75055~28850.8~40
100050~26736~188
75040~26328~185
100040~24928~175
4250VTP400~28
Outlet Size 10" Min Submergence 151cm
125041~30528~214
150040~29228~205
150058~28540~200
200063~25144~176
5250VTP550~26
Outlet Size 10" Min Submergence
171cm
200040~19428~185
200057~26640~187
250061~24543~172
6300VTP860~43
Outlet Size 12" Min Submergence
180cm
250050~24535~172
300053~23537~165
7350VTP860~43
Outlet Size 12" Min Submergence 180cm
250074~23652~166
300069~23048.5~162
350073~22251~156
4000104~20773~145
8350VTP1250~36
Outlet Size 14"
Min Submergence 250cm
350048~25034~176
400046~24433~172
9400VTP1250~36
Outlet Size 16"
Min Submergence 250cm
400061~27043~190
450060~26442~186
5000253178

Standards

NFPA20, UL, FM, EN12845,CCCF
Performance Ranges
UL : Q: 250-5000GPM H:80-300PSI
FM: Q: 250-5000GPM H:80-300PSI
CCCF: Q:15-300L/S H:0.60-2.0Mpa
NFPA20: Q: 250-5000GPM H:80-300PSI


-Manuals

Vertical Turbine Fire Pump

-Data sheet


Vertical Turbine Fire Pump

Metallurgies available for sea/brackish water applications and harsh environments:


  • Stainless steel

  • Duplex and Super Duplex

  • Nickel-Aluminum-Bronze

  • Special materials available on request



FIRE MARKET APPLICATIONS

  • Sprinkler systems

  • Hydrant systems

  • Water curtains