+86-182-9191-0663 丨  sales@hiltechgroup.com | support@hiltechgroup.com

About Us

Since 1998 丨 HILTECH®

You are here: Home » Products » Control & Analysis Instrument » Controllers And Positioner » Flowserve Logix 3200MD Digital HART Positioner

Flowserve Logix 3200MD Digital HART Positioner

Share to:
  • Explosion proof enclosure rated Class I Division 1 Groups B-D, Ex d IIB+H2, AEx d IIB+H2
  • Intrinsically Safe Rated Class I, Div 1, Groups A-G, Ex ia IIC, AEx ia IIC
  • Non-Incendive Class I Div 2 A-D, Ex nA
  • SIL 2
Availability:
Quantity:


Flowserve Logix 3200MD Digital HART Positioner Introduction

Flowserve Logix 3200MD Digital HART positioner utilizes state-of-the-art piezo technology to provide superior performance and reliability. The Logix 3200MD can be easily configured using the local buttons, HART handheld, and SoftTools software.

Logix 3200MD digital positioner is a two-wire 4-20 mA input digital valve positioner. The positioner is configurable through the local user interface. The Logix 3200MD utilizes the HART protocol to allow two- way remote communications with the positioner. The Logix 3200MD positioner can control both double- and single-acting actuators with linear or rotary mountings. The positioner is completely powered by the 4-20 mA input signal. Start up current must be at least 3.6 mA without AO card or 3.85 mA with AO card.


Flowserve Logix 3200MD Digital HART Positioner Feature

  • Local status LED's

  • Local DIP Switches/Calibration Buttons

  • Auto Tuning with dynamic gain selection

  • Utilizes HART 5

  • Simple calibration via local interface


Flowserve Logix 3200MD Digital HART Positioner Specification 



Power Supply

Two-wire, 4-20 mA

10.0 to 30.0 VDC

Compliance Voltage

10.0 VDC @ 20 mA

Effective Resistance

495 Ω @ 20 mA Typical

Add 20 Ω when HART communication active

Communications

HART Protocol

Minimum Operating Current

3.6 mA without AO board

3.85 mA with AO board

Maximum Voltage

30.0 VDC


Computer

Minimum Pentium processor running Windows 95, 98, NT, 2000, XP, 32 MB total memory (64 MB recom- mended), 30 MB available hard disk space, CD-ROM drive

Ports

1 minimum available with 8 maximum possible. (Can also communicate via PCMCIA and USB connections)

HART Modem

RS-232/PCMCIA card/USB

HART Filter

May be required in conjunction with some DCS hardware

HART MUX

MTL 4840/ELCON 2700




-Manuals

Flowserve Logix 3200MD Digital HART Positioner

-Data sheet


Previous: 