Debug Rosemount 8732E using the 475 field communicator

Views: 6     Author: Site Editor     Publish Time: 2022-01-24      Origin: Site

Foundation Fieldbus FF (Foundation Fieldbus) is an all-digital serial two-way communication system used to connect various vacuum gauge calibration equipment - Hiltechintelligent instrument equipment and automation systems in the industrial field. Nowadays, there are more and more projects adopting bus architecture, but not everyone is very familiar with the debugging of FF bus instrument. This article mainly introduces how to debug Rosemount 8732E electromagnetic flowmeter through Emerson's 475 handheld communicator supporting Foundation Fieldbus bus protocol. Everyone It can be applied to the debugging of other instruments by analogy.

Tools needed for debugging: Emerson 475 handheld communicator, AMS Trex handheld communicator.

Menu 475: Online> Device List> AI 3000> Quick Config> Transducer Scale Unit...

1. Select Online, the 475 Communicator will find all online FF devices in the same network segment.

*If the following WARNING message appears, you need to change the hook position of the 475 Communicator.

analog multimeter calibration price - Hiltech

2. Select the 8732 electromagnetic flowmeter to be configured in the list of found FF devices.

*Most on-site tag numbers are******F***.

best emerson 475 communicator - Hiltech

3. Select AI block (AI 3000) in the block list to enter.

buy emerson field communicator - Hiltech

4. Select Quick Config to enter the configuration menu.

cheap emerson hart 475 - Hiltech

5. In the Transducer Scale Unit... display as the current flow unit, select to enter the modification.

*Before making changes, the AI block mode needs to be changed to OOS mode first, see step 6 for details.

custom emerson hart 475 field communicator - HILTECH

6. Click MODE and enter the menu to change the AI block mode to OOS.

*This operation can also be carried out in the previous step 4.

475 communicator company - Hiltech

7. Select the desired flow unit.

475 Field Communicator cost - Hiltech

8. Click SEND to save the changes.

dead weight pressure calibrator for sale - Hiltech

9. The flow unit modification has been saved, and there is a "*" in front of the menu when it is not saved.

vacuum gauge calibration equipment supplier - Hlitech

10. Click MODE to restore the AI block mode to AUTO.

analog multimeter calibration price - Hiltech

11. If the following WARNING message appears during the operation, select YES to continue.

pressure gauge calibration manufacturer - Hiltech