Flowserve Logix 3200MD Digital HART positioner utilizes state-of-the-art piezo technology to provide superior performance and reliability. The Logix 3200MD can be easily configured using the local buttons, HART handheld, and SoftTools software.
Logix 3200MD digital positioner is a two-wire 4-20 mA input digital valve positioner. The positioner is configurable through the local user interface. The Logix 3200MD utilizes the HART protocol to allow two- way remote communications with the positioner. The Logix 3200MD positioner can control both double- and single-acting actuators with linear or rotary mountings. The positioner is completely powered by the 4-20 mA input signal. Start up current must be at least 3.6 mA without AO card or 3.85 mA with AO card.
Local status LED's
Local DIP Switches/Calibration Buttons
Auto Tuning with dynamic gain selection
Utilizes HART 5
Simple calibration via local interface
Power Supply | Two-wire, 4-20 mA 10.0 to 30.0 VDC |
Compliance Voltage | 10.0 VDC @ 20 mA |
Effective Resistance | 495 Ω @ 20 mA Typical Add 20 Ω when HART communication active |
Communications | HART Protocol |
Minimum Operating Current | 3.6 mA without AO board 3.85 mA with AO board |
Maximum Voltage | 30.0 VDC |
Computer | Minimum Pentium processor running Windows 95, 98, NT, 2000, XP, 32 MB total memory (64 MB recom- mended), 30 MB available hard disk space, CD-ROM drive |
Ports | 1 minimum available with 8 maximum possible. (Can also communicate via PCMCIA and USB connections) |
HART Modem | RS-232/PCMCIA card/USB |
HART Filter | May be required in conjunction with some DCS hardware |
HART MUX | MTL 4840/ELCON 2700 |