E+H Proline Prowirl F 200 vortex flow meter offers the preferred measuring principle for wet, saturated or superheated steam, gases and liquids. The meter features a robust, drift-free capacitive sensor for long-term stability, and a separate connection compartment for convenient device wiring. With genuine loop-powered technology, the F 200 enables cost-effective and seamless integration into existing infrastructures. Integrated verification with Heartbeat technology ensures process safety at all times. The Prowirl F 200 also features flexible positioning of the pressure cell, an industrial siphon design for pressure measurement, and a display module with data transfer function.
Measures volume flow, mass flow, energy flow,
heat flow difference, and temperature
DN 25 to 300 (1 to 12in) nominal diameter range
for wet steam
Accuracy:
Up to ±0.65% volume flow
Up to ±0.85% mass flow
Consistent accuracy down to Re 10,000
PN 100, Class 600, 20K maximum process pressure
Medium temperature range:
–40 to 500° F (–40 to 260° C) standard
–328 to 752° F (–200 to 400° C) optional
Inlet run compensation
HART, PROFIBUS PA, FOUNDATION Fieldbus
IP66/67, type 4X enclosure
ATEX, IECEx, cCSAus, JPN, EAC
4‐line backlit display with touch control
Vortex
Versatile flowmeter with detection of wet steam conditions and best-in-class accuracy.
Easy energy management – integrated temperature and pressure measurement for steam and gases.
Suitable for a wide range of applications; optimized for steam applications.
Space-saving engineering – inlet run compensation. Same accuracy down to Re 10 000 – most linear Vortex meter body. Long-term stability – robust drift-free capacitive sensor.
Wet steam capabilities for DN 25 to 300 (1 to 12"). Flexible positioning of pressure cell. Industrial siphon design for pressure measurement.
Space-saving engineering – inlet run compensation. Same accuracy down to Re 10 000 – most linear Vortex meter body. Long-term stability – robust drift-free capacitive sensor.
Wet steam capabilities for DN 25 to 300 (1 to 12"). Flexible positioning of pressure cell. Industrial siphon design for pressure measurement.
Convenient device wiring – separate connection compartment. Safe operation – no need to open the device due to display with touch control, background lighting. Integrated verification – Heartbeat Technology.
Display module with data transfer function. Robust dual-compartment housing. Plant safety: worldwide approvals (SIL, Haz. area).
Convenient device wiring – separate connection compartment. Safe operation – no need to open the device due to display with touch control, background lighting. Integrated verification – Heartbeat Technology.
Display module with data transfer function. Robust dual-compartment housing. Plant safety: worldwide approvals (SIL, Haz. area).
DN 15 to 300 (½ to 12")
Measuring tube: 1.4408 (C3FM); CX2MW similar to Alloy C22, 2.4602
DSC sensor: 1.4404 (316/316L); UNS N06022 similar to Alloy C22, 2.4602
Process connection: 1.4404/F316/F316L); 2.4602
Volume flow, mass flow, corrected volume flow, energy flow, heat flow difference, temperature
Volume flow (liquid): ±0.75 %
Volume flow (optional): ±0.65 %
Volume flow (steam, gas): ±1.00 %
Mass flow (saturated steam): ±1.7% (temperature compensated); ±1.5% (temperature/pressure compensated)
Mass flow (superheated steam, gas): ±1.5 (temperature/pressure compensated); ±1.7% (temperature compensated + external pressure compensation)
Mass flow (liquid): ±0.85%
Liquid: 0.076 to 2100 m⊃3;/h (0.045 to 1300 ft⊃3;/min)
depending on medium: water with 1 bar a, 20 °C (14.5 psi a, 68° F)
Steam, gas: 0.39 to 28000 m⊃3;/h (0.23 to 17000 ft⊃3;/min)
depending on medium: steam with 180 °C, 10 bar a (356 °F, 145 psi a); air with 25 °C, 4.4 bar a (77 °F, 63.8 psi a)
PN 100, Class 600, 20K
Standard: –40 to +260 °C (–40 to +500 °F)
High/low temperature (option): –200 to +400 °C (–328 to +752 °F)
Compact version (standard): –40 to +80 °C (–40 to +176 °F)
Compact version (option): –50 to +80 °C (–58 to +176 °F)
Remote version (standard): –40 to +85 °C (–40 to +185 °F)
Remote version (option): –50 to +85 °C (–58 to +185 °F)
Sensor connection housing: AlSi10Mg, coated; 1.4408 (CF3M)
AlSi10Mg, coated; 1.4404 (316L)
Compact version: IP66/67, type 4X enclosure
Sensor remote version: IP66/67, type 4X enclosure
Transmitter remote version: IP66/67, type 4X enclosure
4‐line backlit display with touch control (operation from outside)
Configuration via local display and operating tools possible
Remote display available
4‐20 mA HART (passive)
4‐20 mA (passive)
Pulse/frequency/switch output (passive)
Current Input 4‐20 mA (passive)
HART, PROFIBUS PA, FOUNDATION Fieldbus
DC 12 to 35 V (4‐20 mA HART with/without pulse/frequency/switch output)
DC 12 to 30 V (4‐20 mA HART, 4‐20 mA)
DC 12 to 35 V (4‐20 mA HART, pulse/frequency/switch output, 4‐20 mA input)
DC 9 to 32 V (PROFIBUS PA, pulse/frequency/switch output)
ATEX, IECEx, cCSAus, JPN, EAC
CE, C-TICK, EAC
Functional safety according to IEC 61508, applicable in safety-relevant applications in accordance with IEC 61511
Calibration performed on accredited calibration facilities (acc. to ISO/IEC 17025)
Heartbeat Technology complies with the requirements for measurement traceability according to ISO 9001:2015 – Section 7.1.5.2 a (TÜV SÜD attestation)
ABS, LR, BV, DNV GL
PED, CRN, AD 2000
3.1 material
NACE MR0175/MR0103, PMI (on request); welding test acc. to ISO 15614‐1, similar to ASME IX (on request)
-Manuals
Proline Prowirl F 200 Vortex Flow Meter
-Data sheet